Substation Safety and Equipment

Log in

Made with ScholarlyMake flashcards like these from your own notes

Substation Safety and Equipment

Questions and answers

92 cards
  1. Question:Please list the Six (6) major categories of discussion for any Tailboard:

    Answer:Methods of emergency notification; the job plan; job hazards; what is energized and what is not, including clearance points; assignments, groups, or individuals; special precautions, special equipment, and PPE; and questions from participants.

  2. Question:What is the proper procedure for tagging open disconnect switches?

    Answer:Inspect the disconnect. Contact PDO to receive a clearance on it. Complete a “Do not operate” tag with the clearance number, name, date, and contact information. Attach the tag to the disconnect while it is open and locked.

  3. Question:What can result from removing another person’s tag and operating the switch without proper authority?

    Answer:It could cause injury or death to personnel, damage property, and result in termination.

  4. Question:What safe working distances are listed for qualified and unqualified personnel in 230 kV and 500 kV yards?

    Answer:230 kV: unqualified, 13’0”; qualified, P-G 5’8” and P-P 8’5”. 500 kV: unqualified, 18’0”; qualified, 20’4”.

  5. Question:Which basic safe work practices apply in 230 kV or 500 kV receiving stations?

    Answer:Check in by phone or sub-entry software; keep unmonitored gates closed and locked; follow posted traffic signs; observe overhead clearances to energized conductors and qualified and unqualified MADs; use PPE; and inform personnel of your presence and tailboard with the crew.

  6. Question:What clearance distance above ground is listed for personnel safety at 12 kV?

    Answer:9’0”.

  7. Question:What clearance distance above ground is listed for personnel safety at 69 kV?

    Answer:10’5”.

  8. Question:What clearance distance above ground is listed for personnel safety at 230 kV?

    Answer:13’9”.

  9. Question:What clearance distance above ground is listed for personnel safety at 500 kV?

    Answer:20’6”.

  10. Question:At what elevation do minimum approach distances change, and how do they change above it?

    Answer:Above 3,000 feet above sea level, MADs increase by a correction factor found in Appendix A of the APR.

  11. Question:What voltage range classifies an electrical circuit as secondary?

    Answer:A circuit that normally operates at less than 600 volts is classified as secondary.

  12. Question:What voltage range classifies an electrical circuit as primary?

    Answer:A circuit that normally operates at 600 volts or more is classified as primary.

  13. Question:Why must potential transformers be isolated before work on a 12 kV switchgear bus?

    Answer:To eliminate the possibility of back-feed. Primary conductors and equipment, including PTs and CPTs, are considered energized until isolated from all primary and secondary voltage sources, tested for voltage, and grounded in accordance with PPG Standards.

  14. Question:Which precautions apply when employees install or maintain batteries?

    Answer:Only qualified employees may install or maintain batteries and associated equipment. Smoking, open flames, and other combustion ignition sources are prohibited near batteries.

  15. Question:Which protective measures are required when handling acids or damaged batteries?

    Answer:Wear a rubber apron, face shield, and appropriate hand and eye protection. Ensure eyewash provisions are available near the work area.

  16. Question:What is an indeterminate under substation clearance standards, and which examples are given?

    Answer:It is non-conductive, ungrounded material or apparatus that could have voltage on it. Examples include an insulator, the outside of a bushing, and ungrounded metal parts.

  17. Question:Who can release a clearance?

    Answer:The clearance holder or an immediate supervisor.

  18. Question:How far must a ladder extend above its supporting structure?

    Answer:A minimum of 3 feet.

  19. Question:What does back-feed mean in an electrical circuit?

    Answer:The intentional or unintentional energization of a circuit outside its normal source. Generators providing temporary power are an example.

  20. Question:Which precautions must be completed before entering a manhole?

    Answer:Conduct and complete a pre-entry tailboard; complete the enclosed-space entry checklist to determine whether a confined-space permit is required; test for a hazardous atmosphere; ventilate the space; set up rescue equipment; ensure 100% tethering; barricade the area; and assign an outside attendant to maintain contact.

  21. Question:What steps are required before entering an energized vault?

    Answer:De-energize it if possible; if not, obtain management approval. DOC/TGO must complete the Enclosed Space Emergency Switching Form. Have the test group perform IR imaging for hot spots; IR-scan and blanket any splices; have a qualified person ready to rack out the breaker if needed to isolate the space; and obtain a hold tag for circuits inside the vault.

  22. Question:Who may work in an energized vault under the stated requirements?

    Answer:An electrically qualified person may work in an energized vault. The listed staffing condition is 2 journeymen and/or a hot apprentice under a journeyman’s direct supervision.

  23. Question:What minimum crew size is specified for work in an energized vault?

    Answer:Three or more, based on the job scope.

  24. Question:What does Blue Stake Service do, and when must it be completed?

    Answer:It determines the location of and marks underground utilities in the work area. It must be completed before excavation outside a substation.

  25. Question:How much time does Blue Stake Service require to perform its function?

    Answer:Two full workdays.

  26. Question:What is a hold tag used to indicate?

    Answer:It is an approved tag or card warning against operation of a particular switch, device, circuit, tool, machine, gate, or other equipment. It may also indicate disabling a breaker or recloser’s reclosing operation.

  27. Question:What characterizes a diminished hold tag on a ground relay?

    Answer:The timing (51G), rather than instantaneous (50G), portion of the ground relay has been disabled. This raises the tripping current level and the safety threshold.

  28. Question:What happens when the re-closure toggle switch is moved to the off position?

    Answer:It prevents a breaker from automatically closing.

  29. Question:At what trench depth is cave-in protection required for an employee’s entry?

    Answer:At least 5 feet deep.

  30. Question:What does M.O.D. stand for in substation equipment terminology?

    Answer:Motor operated disconnect.

  31. Question:What is a C.C.V.T., and what function does it perform?

    Answer:A capacitive coupled voltage transformer uses capacitors in series to step down extra-high voltage and provide a low-voltage signal for measurement or operation of a protective relay.

  32. Question:How does a potential transformer support substation metering and protection?

    Answer:A potential transformer is an instrument transformer that converts higher voltage values to lower values for metering, protection and control devices, and load survey.

  33. Question:How does a control power transformer supply substation AC circuits?

    Answer:It steps down primary voltage to a usable secondary voltage, supplying AC circuits such as station services, battery chargers, and HVAC systems. It may be in switchgear, pad- or pole-mounted, or supplied from outside the substation.

  34. Question:How does a current transformer make high current useful for monitoring?

    Answer:It steps down high current to a usable level for metering, relaying, and monitoring.

  35. Question:When might a mobile unit transformer be used, and what does it provide?

    Answer:It is a mobile substation used to provide temporary power for customers in emergencies.

  36. Question:How does a load tap changer help maintain transformer output voltage?

    Answer:Connected to power transformers and in series with the low-side windings, it provides a stable and correct secondary output voltage as load demand changes.

  37. Question:How does an automatic transfer switch respond to loss of primary AC voltage?

    Answer:It detects loss of AC voltage from the primary source and automatically switches power from the primary source to the secondary source. It is used for construction and maintenance purposes and is typically found in EHV yards.

  38. Question:What role does a bus serve between electrical equipment?

    Answer:A bus is a set of conductors carrying power that acts as a common connection point between electrical equipment.

  39. Question:How does a transformer protector differ from a normal circuit breaker, and when is it used?

    Answer:It operates as a normal circuit breaker but does not have CTs. It isolates a transformer during a fault or catastrophic failure, such as an internal fault or rapid pressure rise relay event.

  40. Question:What do ACB and VCB stand for in substation equipment terminology?

    Answer:ACB means air circuit breaker. VCB means vacuum circuit breaker.

  41. Question:Which physical configuration describes a KPF switch?

    Answer:An overhead, 3-phase, gang-operated switch that is pole-mounted.

  42. Question:What does PRL refer to in substation equipment terminology?

    Answer:A pole-mounted gang-operated load break switch.

  43. Question:Which characteristics identify a PE device?

    Answer:A pad-mounted live-front device with exposed energized components greater than 600 volts.

  44. Question:What path does a pole riser provide between underground and overhead systems?

    Answer:It carries the transition from underground cable to overhead lines.

  45. Question:How does a pad-mounted PE differ from a pad-mounted PD?

    Answer:A PE is live-front with exposed conductors. A PD is dead-front, has no exposed energized conductors above 600 V, and uses an effectively grounded metallic shield. Both may be switches, transformers, or capacitor banks.

  46. Question:What does yellow lining indicate on an electrical print?

    Answer:Verification of connection points on the print.

  47. Question:Which color indicates a deletion on an electrical print?

    Answer:Green.

  48. Question:Which color indicates an addition on an electrical print?

    Answer:Red.

  49. Question:Which equipment number refers to a Transformer Protector in SRP’s bay and equipment numbering sequence?

    Answer:#5.

  50. Question:Which insulating mediums are used in EHV breakers?

    Answer:Sulfur Hexafluoride (SF6 Gas) and Mineral Oil.

  51. Question:What is used to adjust the secondary voltage of a distribution transformer?

    Answer:LTC (Load tap Changer).

  52. Question:What is the basic purpose of an LTC?

    Answer:To adjust the output voltage based off the load demand. It adjusts low side voltage.

  53. Question:How does a vacuum interrupter bottle interrupt electric current?

    Answer:Its sealed, vacuum-tight chamber contains electrical contacts. When the contacts open, it extinguishes the electrical arc.

  54. Question:How does an auto transformer differ from a standard distribution 69/12.5kv transformer?

    Answer:An auto transformer has one set of windings. A standard distribution transformer has two sets of windings per phase.

  55. Question:How does a bushing differ from an insulator?

    Answer:A bushing has a current-carrying conductor that allows voltage and current to flow through a grounded plane. An insulator is a solid support structure with no current-carrying capability.

  56. Question:What is the phone call sequence to obtain a clearance on an Industrial substation?

    Answer:Conduct a switching tailboard with the customer. Call PDO for switching instructions; the crew completes the switching and notifies PDO. PDO issues clearance to you if all switching is complete at that time.

  57. Question:What is meant by supervisory control?

    Answer:The remote operation of equipment by TGO or DOC.

  58. Question:What means are provided for isolating potential transformers from the de-energized bus in 12kv switchgear?

    Answer:Rack out the PT drawer, verify the fuse tabs hit the ground tabs or ground braid, and remove the PT fuses.

  59. Question:What is a normal open, and what purpose does it serve in the SRP distribution system?

    Answer:It is an open point in a circuit used for switching and for paralleling load for construction or maintenance purposes.

  60. Question:Which steps ensure that an MOD will not operate during maintenance or construction activities?

    Answer:Place 43M in Maintenance/Local position, remove control power in the control panel, and lock and tag it in the de-coupled and open position.

  61. Question:How does a 43S switch differ from a 43M switch?

    Answer:43M is located in the breaker’s control cabinet. In Maintenance/Local position, it isolates the device from supervisory control, indication, and relay monitoring. 43S is typically in the control house; it isolates supervisory from local control but allows relay monitoring and indication.

  62. Question:What supplies the trip voltage for 12kv breakers?

    Answer:The battery charger under normal circumstances; the battery bank if the battery charger (and AC voltage) is lost.

  63. Question:Why do substations have DC voltages?

    Answer:DC voltages power equipment if AC power is lost. Battery-powered DC systems shall operate for at least 8 hours without support from the AC power system.

  64. Question:What is the objective of substation grounding?

    Answer:It carries and dissipates electrical currents into the earth under normal and fault conditions, helps protect nearby personnel from electrical shock, provides a low-resistance path to earth for lightning strikes and switching surges, and provides a low-impedance return path for neutral current and a ground reference point.

  65. Question:What should be grounded in a substation?

    Answer:All metal equipment and structures inside the ground-grid perimeter, including drop poles, fencing, and walls, are solidly grounded to the station ground grid.

  66. Question:Which safety precaution should be used to repair a broken ground?

    Answer:Use a hot stick to install a jumper across the broken ground to ensure you do not put yourself in series.

  67. Question:What is the minimum standard depth for the ground grid below finished grade?

    Answer:1.5 feet below finished grade. This includes the ABC coverage but excludes surface material used to decrease touch and step potential.

  68. Question:How far should the ground grid extend beyond a substation enclosure and outward-swinging gates?

    Answer:At least three feet beyond the enclosure and three feet beyond the swing radius of any outward-swinging gates.

  69. Question:Which precautions are specified for cad-welding?

    Answer:Conduct a proper tailboard; use the correct mold and shot size; wear proper PPE, including a hard hat, leather gloves, safety glasses, FR clothing, safety-toe boots, and a face shield; have a fire extinguisher; ensure proper ventilation; watch for flammable surfaces; and keep all crew and equipment clear.

  70. Question:How does a station riser differ from an underground feeder riser?

    Answer:A station riser goes from an overhead circuit underground for station service and feeds the whole circuit. An underground or distribution riser feeds a portion of the circuit.

  71. Question:Why do electrical substations and switchyards have AC voltages?

    Answer:They require auxiliary power for operation and maintenance. AC power serves outlets, yard lighting, transformers, HVAC units, and battery chargers, and provides convenience power for maintenance and construction activities.

  72. Question:15. An adequate ground grid design in the SRP system is one in which the resistance to remote earth is less than what value?

    Answer:0.5Ω

  73. Question:16. Fill in the blank: Above ground connections and equipment connections shall be made using ___, ____ or __ connections based on the maximum expected pigtail temperature calculated in the design.

    Answer:Compression, bolted, or welded

  74. Question:17. What is SRP’s standard conductor size for all new ground grid instillations?

    Answer:4/0 copper 7 strand conductor

  75. Question:18. What print section is our Grounding prints?

    Answer:5

  76. Question:19. What is a grounding electrode?

    Answer:A conductive object embedded into the earth that connects an electrical system to reference ground, usually earth.

  77. Question:20. Grounding Electrodes shall be installed where when installing a ground grid?

    Answer:Always place a ground rod at each point where surge arrestor loops are connected to the ground grid. Always place a ground rod at each outside corner of the grid

  78. Question:21. What does PPG stand for?

    Answer:Personal Protection Grounds

  79. Question:22. When is a ground grid test needed?

    Answer:After all construction excavations are complete and no more disturbance of earth in conjunction with the construction is anticipated for the job, or after disturbance of earth greater than 12” deep.

  80. Question:23. What is the maximum number of 90° bends in a single conduit run? Why?

    Answer:No more than 360 degrees (4 Bends), this is to prevent damaging the wires when pulling.

  81. Question:25. What is the difference between EMT and rigid conduit?

    Answer:EMT is a thin wall conduit and uses compression fittings. RMC has thicker walls and uses threaded connectors; rigid conduit is more durable.

  82. Question:26. What are the three basic steps to bending a (3 point) saddle?

    Answer:First bend your 45-degree bend. Then bend 22.5-degree bends on each end.

  83. Question:27. In terms of bending conduit, what is the constant multiplier?

    Answer:10°: 6; 22.5°: 2.6; 30°: 2; 45°: 1.4; 60°: 1.2.

  84. Question:Which four objectives does substation grounding serve?

    Answer:It carries and dissipates electrical currents into earth under normal and fault conditions without exceeding operating and equipment limits; protects nearby personnel from electric shock; provides a path to earth for lightning impulses and switching surges; and provides a low-impedance return path for neutral current and a ground reference point for the electrical system.

  85. Question:How does the low-impedance grounding path serve the electrical system?

    Answer:It provides a return path for neutral current and serves as a ground reference point for the electrical system.

  86. Question:Why does substation grounding need to dissipate current without exceeding equipment limits?

    Answer:Its objective is to carry and dissipate electrical currents into earth under normal and fault conditions without exceeding operating and equipment limits.

  87. Question:How does a ground grid help protect nearby personnel?

    Answer:It helps ensure that personnel in the vicinity of grounded facilities are not exposed to the danger of electric shock.

  88. Question:Which multiplier applies to a 10° conduit bend?

    Answer:6

  89. Question:Which multiplier applies to a 22.5° conduit bend?

    Answer:2.6

  90. Question:Which multiplier applies to a 30° conduit bend?

    Answer:2

  91. Question:Which multiplier applies to a 45° conduit bend?

    Answer:1.4

  92. Question:Which multiplier applies to a 60° conduit bend?

    Answer:1.2