Physical specs of the 132kV LCC: dimensions, steel enclosure, mimic panel, and Local/Remote selector.
How non-critical AC heaters and lighting differ from the critical 220 V DC that feeds trips, relays, and motors.
Inserting a hand crank depresses a limit switch and hard-wires the motor DC supply off for technician safety.
Trip-circuit supervision, anti-pumping, SF6 density blocking, and redundant Trip 2 protect the main breaker.
Double-operation, load interlocking, maintenance lockout, and breaker-release logic prevent dangerous switching.
Mimic LEDs, KFAL fault relays, the PBAL1 annunciator, and lamp test keep operators informed.
CT/VT test disconnects and the front-panel multimeter complete the LCC as the bay control interface.