132kV GIS Local Control Cabinet Schematic Walkthrough

0:00 / 4:52
LCC overview
0:00 - 0:45

Physical specs of the 132kV LCC: dimensions, steel enclosure, mimic panel, and Local/Remote selector.

AC vs DC auxiliaries
0:45 - 1:31

How non-critical AC heaters and lighting differ from the critical 220 V DC that feeds trips, relays, and motors.

Hand-crank motor lockout
1:31 - 2:10

Inserting a hand crank depresses a limit switch and hard-wires the motor DC supply off for technician safety.

Circuit breaker -QA1 control
2:10 - 2:53

Trip-circuit supervision, anti-pumping, SF6 density blocking, and redundant Trip 2 protect the main breaker.

Bay-wide interlocking
2:53 - 3:32

Double-operation, load interlocking, maintenance lockout, and breaker-release logic prevent dangerous switching.

Status, faults, and lamp test
3:32 - 4:13

Mimic LEDs, KFAL fault relays, the PBAL1 annunciator, and lamp test keep operators informed.

Measurement and close
4:13 - 4:52

CT/VT test disconnects and the front-panel multimeter complete the LCC as the bay control interface.